The DUNGS MB-D(LE) 415–420 B01 MultiBloc combines multiple gas train functions into one compact and efficient unit. Designed for larger gas burner applications, it integrates filtration, pressure monitoring, pressure regulation, and automatic safety shut-off valves, reducing installation complexity while improving operational safety.
Available in DN40 and DN50 sizes, the MB-D(LE) 415–420 B01 is suitable for industrial combustion systems requiring high gas flow capacity and precise pressure control. The integrated design minimizes external piping and simplifies burner assembly.
The unit is available in standard MB, MB-D, MB-LE, and MB-DLE versions, providing flexibility for various burner control requirements.
Key Features
Integrated gas train solution
One-stage gas control operation
Built-in microfilter
Integrated gas pressure switch
Adjustable gas pressure regulator
Dual automatic safety shut-off valves
Compact design for high-capacity burners
Reliable gas flow and pressure control
Suitable for industrial combustion systems
VPS 504 valve proving system compatible
KO1/1 closed position signal contact compatible
Easy installation and maintenance
Applications
Industrial Gas Burners
Commercial Gas Burners
Steam Boilers
Hot Air Generators
Industrial Furnaces
Thermal Oil Heaters
Process Heating Equipment
Drying Systems
Combustion Systems
OEM Burner Manufacturing
Why Choose DUNGS MB-D(LE) 415–420 B01?
High-capacity gas flow handling
Combines multiple gas train components in one unit
Improves burner safety and reliability
Reduces installation time and piping requirements
Provides accurate gas pressure regulation
Compact and space-saving design
Compatible with burner safety monitoring systems
Trusted DUNGS gas control technology
Technical Description
The DUNGS MB-D(LE) 415–420 B01 MultiBloc integrates a gas filter, optional pressure switch, pressure regulator, and two safety shut-off valves into a single assembly for one-stage burner operation.
The system includes:
V1 = Double-seat safety valve
V2 = Double-seat safety valve
Integrated microfilter
Optional gas pressure switch
Adjustable pressure regulator
The unit supports inlet pressures up to 200 mbar and outlet pressure ranges of 4–20 mbar or 4–50 mbar depending on the configuration. For additional safety monitoring, the system can be equipped with a VPS 504 Valve Proving System.
For high-flow applications, the filter element can be removed and an external DUNGS GF gas filter can be installed upstream.
Technical Specifications
Specification | Details |
|---|---|
Brand | DUNGS |
Series | MB-D(LE) 415–420 B01 |
Product Type | Gas MultiBloc |
Function | One-Stage Gas Control |
Nominal Sizes | DN40, DN50 |
Maximum Inlet Pressure | Up to 200 mbar |
Outlet Pressure Range | 4–20 mbar / 4–50 mbar |
Filter | Integrated Microfilter |
Pressure Switch | Optional |
Pressure Regulator | Integrated |
Valve Configuration | Double-Seat Safety Valves |
Valve Proving System | VPS 504 Compatible |
Available Models
Model | Nominal Size | Valve Configuration |
MB-D(LE) 415 B01 | DN40 | Double-Seat Valves |
MB-D(LE) 420 B01 | DN50 | Double-Seat Valves |
Main Components
Component | Function |
Filter (3) | Removes contaminants from gas flow |
Pressure Switch (4) | Monitors gas pressure |
Regulator (5) | Controls outlet gas pressure |
Valve V1 | Double-seat safety shut-off valve |
Valve V2 | Double-seat safety shut-off valve |
Available Versions
Version | Description |
MB | Standard MultiBloc |
MB-D | Main Volume Restrictor |
MB-LE | Adjustable Opening Behaviour |
MB-DLE | Combination of D and LE Functions |